Description
Halogen Free insulated and sheathed cable is used in indoor fixed installations, in dry or humid places, for signal and data transmission. The cable, which has a static screen, is protected against electromagnetic interference from the environment. It is used in fire alarm system between control panel and detectors, buttons and field control modules. Since halogen-free material is used in the cable structure (it does not transmit flames late, does not emit toxic gas after combustion and does not create black smoke that prevents vision), it is used in buildings where people are dense, especially in places that should not be affected by fire conditions.
Be the first to review “JH(St)H…Lg”
| temperature range | -30 °C… +70 °C |
| Bending radius min. | 10 x D |
| Loop resistance | Ø 0,60mm max. 130 Ω/km Ø 0,80mm max. 73.2 Ω/km Ø 1.0 mm max. 44.4 Ω/km 1.0 mm2 max. 36.2 Ω/km 1.5 mm2 max. 24.2 Ω/km 2.5 mm2 max. 14.8Ω/km |
| Insulation resistance min. | 100MΩx km |
| Capacitance max. | 100nF/km |
| Capacity imbalance max. | 300pF/100m |
| Test voltage | 800 Vac core/core 800 Vac core/display |
| Operating voltage max. | 300V |
| standards | TSE K 173, DIN VDE 0815 |
| fire performance | Vertical flame spread EN 60332-1-2
Corrosive gas EN 60754-1/2 Smoke density EN 61034-2 |
| EU declaration of conformity | LVD Low Voltage Directive 2014/35/EU
RoHS Restriction of Use of Certain Hazardous Substances |