Description

PVC insulated and sheathed cable is used in indoor fixed installations, in dry or humid places, for signal and data transmission. The cable, which has a static screen, is protected against electromagnetic interference from the environment. It is used in fire alarm system between control panel and detectors, buttons and field control modules.

Avis

Il n’y a pas encore d’avis.


Soyez le premier à laisser votre avis sur “JY(St)Y…Lg”

temperature range -30 °C… +70 °C
Bending radius min. 10 x D
Loop resistance Ø 0,60mm max. 130 Ω/km
Ø 0,80mm max. 73.2 Ω/km
Ø 1.0 mm max. 44.4 Ω/km
1.0 mm2 max. 36.2 Ω/km
1.5 mm2 max. 24.2 Ω/km
2.5 mm2 max. 14.8Ω/km
Insulation resistance min. 100MΩx km
Capacitance max. 100nF/km
Capacity imbalance max. 300pF/100m
Test voltage 800 Vac core/core
800 Vac core/display
Operating voltage max. 300V
standards TSE K 173, DIN VDE 0815
fire performance Vertical flame spread EN 60332-1-2
EU declaration of conformity LVD  Low Voltage Directive 2014/35/EU 

RoHS Restriction of Use  of Certain Hazardous Substances
2011/65/EU